Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11CM02877
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02877
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2011 GERRY KOZIOL WWM REVIEW Passed
09/08/2011 DAVE MANN FIRE REVIEW Approved
09/15/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide special inspection certifications as required by the structural engineer specifications on sheet M6.2.
2. Please provide structural calculations for all new roof top units and/or documation that the replacement units are equal in weight or less than those being replaced.
END OF REVIEW
09/20/2011 ROBERT SHERRY WATER REVIEW Approved
09/20/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the gas load for IRH-29 and IRH-30 in the total gas load for the medium-pressure gas meter. Reference: Section 402.2, IFGC 2006.
2. Clarify the total gas load for the regulator serving IRH-29 and IRH-30; does the 120 CFH load include an additional 60 CFH future load? Reference: Section 402.2, IFGC 2006
09/21/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify details 1/M6.2, 3/M6.2 and 5/M6.2; coordinate the detail tags with the plans.
2. Fan coil FC-2.3 is scheduled to receive 160 CFM of outside air. Show the source of the outside air. Reference: Section 106.3.1, IMC 2006.
3. Indicate what is being exhausted from the slot hood (detail 1/M6.2) and how the location of the exhaust outlet complies with the requirements of Section 501.2.1, IMC 2006.
09/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/28/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/28/2011 SUE REEVES REJECT SHELF Completed