Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02877
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/08/2011 | GERRY KOZIOL | WWM | REVIEW | Passed | |
09/08/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
09/15/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide special inspection certifications as required by the structural engineer specifications on sheet M6.2. 2. Please provide structural calculations for all new roof top units and/or documation that the replacement units are equal in weight or less than those being replaced. END OF REVIEW |
09/20/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/20/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Include the gas load for IRH-29 and IRH-30 in the total gas load for the medium-pressure gas meter. Reference: Section 402.2, IFGC 2006. 2. Clarify the total gas load for the regulator serving IRH-29 and IRH-30; does the 120 CFH load include an additional 60 CFH future load? Reference: Section 402.2, IFGC 2006 |
09/21/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify details 1/M6.2, 3/M6.2 and 5/M6.2; coordinate the detail tags with the plans. 2. Fan coil FC-2.3 is scheduled to receive 160 CFM of outside air. Show the source of the outside air. Reference: Section 106.3.1, IMC 2006. 3. Indicate what is being exhausted from the slot hood (detail 1/M6.2) and how the location of the exhaust outlet complies with the requirements of Section 501.2.1, IMC 2006. |
09/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/28/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
09/28/2011 | SUE REEVES | REJECT SHELF | Completed |