Permit Number: T11CM02851
Parcel: 12809016D

Address:
4701 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T11CM02851
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/01/2011 RONALD BROWN HC SITE REVIEW Denied NON RESPONSIVE-SAME COMMENTS AS PER LAST RESUBMITTAL

1. In first submittal comment number 5, it was required that all slopes be shown on the accessible parking detail as per Section 502. Section 502.5 calls for the maxium slopes in all directions be 2% maximum. As per sheet 3, you have a 3.3% slope at the westerly side of the accessible parking space.
2. As per the first submittal comment number 6, all slope requirements for the curb ramp was to be shown. Missing in the detail "PARKING SPACE DETAIL (on sheet C4.1) is the center ramp slope of 1:12 maximum, the parking and aisle area slope as per ICC~ANSI 117.1, Section 406.1, 502.2. Also, reference Note 8 pointing to the ramp, to Sheet 2.
END OF REVIEW
12/02/2011 ANDREW CONNOR LANDSCAPE REVIEW Approved