Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02841
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02841
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, and 504.4, IMC 2006.
2. Comment not addressed. Show how the dryer installation complies with Section 504.5, IMC 2006.
09/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Install the expansion tank on the cold water inlet to the water heater and with no valves between the water heater and the expansion tank. reference: Section 310.4, UPC 2006.
2. The washing machine drain box cannot physically accommodate the T&P relief, the water heater pan drain, and the washing machine discharge with one 2" standpipe.
09/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT: SHEET E2.0; DETAIL 3: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE.
2. PREVIOUS COMMENT: SHEET MP1.0; DETAIL 5: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE.
09/15/2011 CAGUILA1 WWM REVIEW Needs Review
09/15/2011 CAGUILA1 ENGINEERING REVIEW Needs Review