Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02841
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/08/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, and 504.4, IMC 2006. 2. Comment not addressed. Show how the dryer installation complies with Section 504.5, IMC 2006. |
| 09/08/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Install the expansion tank on the cold water inlet to the water heater and with no valves between the water heater and the expansion tank. reference: Section 310.4, UPC 2006. 2. The washing machine drain box cannot physically accommodate the T&P relief, the water heater pan drain, and the washing machine discharge with one 2" standpipe. |
| 09/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT: SHEET E2.0; DETAIL 3: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE. 2. PREVIOUS COMMENT: SHEET MP1.0; DETAIL 5: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE. |
| 09/15/2011 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 09/15/2011 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |