Permit Number: T11CM02841
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02841
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2011 STEVE SHIELDS ZONING REVIEW Approved
09/01/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, and 504.4, IMC 2006.
2. Show how the dryer installation complies with Section 504.5, IMC 2006.
09/01/2011 ERIC NEWCOMB ADA REVIEW Passed
09/01/2011 ROBERT SHERRY WATER REVIEW Approved
09/01/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A2.0; PROPOSED PLAN: PROVIDE DETAILS FOR THE BRACING OF NEW INTERIOR PARTITION WALLS TO RESIST HORIZONTAL LOAD SPECIFIED IN THE IBC SECTION 1607.13. INCLUDE BRACING SIZE AND SPACING, CONNECTION OF THE BRACING TO THE TOP OF THE WALL, AND THE CONNECTION OF THE BRACING TO THE EXISTING STRUCTURE ABOVE.
2. SHEET E2.0; DETAIL 3: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE.
3. SHEET MP1.0; DETAIL 5: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE.
09/01/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping for the water heater. Reference: Section 504.5, IECC 2006.
2. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference: Section 608.3, UPC 2006 with local amendments.
3. Clarify the termination points of the T&P relief pipe and the pan drain; the detail specifies a floor drain but there doesn't appear to be one in the area of the water heater. Reference: Sections 608.5 and 804.1, UPC 2006.
09/01/2011 MARTIN BROWN FIRE REVIEW Approved
09/01/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/08/2011 DROBEY1 WWM REVIEW Needs Review
09/08/2011 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review T11cm02841
5870 E Broadway 315

Electrical notes: Sheet E-2 shows a dryer either in combo with the washer or on it's own, how is the dryer powered ?
Not shown in panel.

Ray Majuta
Elect Pln CK
PDSD,C of Tuc
9/1/11
520/837/4988
09/08/2011 DROBEY1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2011 DELMA ROBEY OUT TO CUSTOMER Completed