Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02841
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/01/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
09/01/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, and 504.4, IMC 2006. 2. Show how the dryer installation complies with Section 504.5, IMC 2006. |
09/01/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
09/01/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/01/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A2.0; PROPOSED PLAN: PROVIDE DETAILS FOR THE BRACING OF NEW INTERIOR PARTITION WALLS TO RESIST HORIZONTAL LOAD SPECIFIED IN THE IBC SECTION 1607.13. INCLUDE BRACING SIZE AND SPACING, CONNECTION OF THE BRACING TO THE TOP OF THE WALL, AND THE CONNECTION OF THE BRACING TO THE EXISTING STRUCTURE ABOVE. 2. SHEET E2.0; DETAIL 3: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE. 3. SHEET MP1.0; DETAIL 5: PROVIDE DESIGN AND DETAIL PER THE CONTRACTOR NOTE. |
09/01/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide 0.5" of insulation with a maximum conductivity of 0.27 BTU per inch/h F on the first 8 feet of supply and discharge piping for the water heater. Reference: Section 504.5, IECC 2006. 2. All storage-type water heaters require a listed expansion tank. Please show expansion tanks on plans. Reference: Section 608.3, UPC 2006 with local amendments. 3. Clarify the termination points of the T&P relief pipe and the pan drain; the detail specifies a floor drain but there doesn't appear to be one in the area of the water heater. Reference: Sections 608.5 and 804.1, UPC 2006. |
09/01/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
09/01/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
09/08/2011 | DROBEY1 | WWM | REVIEW | Needs Review | |
09/08/2011 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | T11cm02841 5870 E Broadway 315 Electrical notes: Sheet E-2 shows a dryer either in combo with the washer or on it's own, how is the dryer powered ? Not shown in panel. Ray Majuta Elect Pln CK PDSD,C of Tuc 9/1/11 520/837/4988 |
09/08/2011 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/08/2011 | DELMA ROBEY | OUT TO CUSTOMER | Completed |