Permit Number: T11CM02840
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02840
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Install the expansion tank on the cold water inlet to the water heater and with no valves between the water heater and the expansion tank. Reference: Section 310.4, UPC 2006.
2. The washing machine drain box cannot physically accommodate the T&P relief, the water heater pan drain, and the washing machine discharge with one 2" standpipe.
09/08/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the size, route, and termination of the dryer exhaust duct. Reference: Sections 504.1, 504.2, and 504.4, IMC 2006.
09/09/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/15/2011 CAGUILA1 WWM REVIEW Needs Review