Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T11CM02807
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/07/2011 | LHANLY1 | NPPO | REVIEW | Passed | |
| 09/07/2011 | LEE HANLY | BUILDING-RESIDENTIAL | REVIEW | Denied | PP A3.0 CLARIFY CRICKET LINES AT NORTH WEST OF FAMILY ROOM...IS THIS JUST ERRATA? PP M1.0 1) CLARIFY REFERENCE TO G2427 FOR EXHAUST FANS IN MASTER BATH. 2) CLARIFY NOTED SUPPLY DIFFUSER WITH NOTE INDICATING "NEW DOUBLE METAL LINER VENT..." AT SOUTH-EAST CORNER OF BASEMENT AREA 3) CLARIFY NOTE ASKING FOR "MINIMUM OPENINGS OF 20" SQUARE FOR DUCT WORK IN TRUSS SPACE". IS NOTE SIMPLY POINTING TO WRONG LOCATION IN TRUSSES, OR ARE YOU FAILING TO INDICATE OTHER DUCTING? 4) SPECIFY INSULATION VALUE OF ALL NEW DUCT WORK PER IRC N1103.2. PP P1.0 SPECIFY INSULATION OF HOT WATER RECIRCULATION SYSTEM PER IRC N1103..4 PPE1.0 1) PLEASE RECALCULATE LOADS FOR EACH PANEL. 400 AMP PANEL SHOWING "EXISTING" DOES NOT PROVIDE SUFFICIENT INFORMATION. ASSUMING THAY "WHOLE HOUSE" LOAD SHOWN AS 177 A IS ON 400 A PANEL HOW DO YOU ACCOUNT FOR THE 178 A ON PANEL A; AND WHERE IS 46 A PANEL B LOAD WHICH IS FED FROM PANEL A? WHERE ARE LOADS TO GUEST HOUSE? IDENTIFY LOCATIONS OF PANEL A AND PANEL B 2) GFCI PLUG RECEPTACLES REQUIRED FOR KITCHEN, BATH AND EXTERIOR. |