| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 09/01/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/07/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | LIGHTING PLAN NOT INCLUDED IN CONSTRUCTION DRAWINGS. 1) SHOW LOCATION OF GARAGE PANEL 2) PROVIDE PANEL SCHEDULE & LOAD CALCULATIONS FOR GARAGE PANEL 3) PROVIDE AVAILABLE FAULT CURRENT CALCULATIONS YOU MAY PROVIDE SINGLE PLAN SHEET WITH TYPICAL INSTALLATION DIAGRAM AS LONG AS PANEL SCHEDULE & LOADS ARE ON SAME SHEET. SITE PLAN WILL REQUIRE LOCATION OF GARAGE PANEL TO BE SHOWN. PLEASE CONTACT LEERAY FOR POSSIBLE OVER-THE-COUNTER REVIEW OF REVISED ELECTRIC PLAN. 837-4906 OR 909-5154 |