Permit Number: T11CM02790
Parcel: 117130410

Address:
44 E BROADWAY BL

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02790
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied Please re-identify scope of work as shell improvemnent as this work does not directly apply to a tennant space.

Clarify project data. Currently it is stated that there is no change to existing egress but 1st floor modifications are to egress route.

Provide detailed dimensioned floor plan for alteration of egress route:

a) Verify actual dimensions for opening into existing ramp. Justify size of door, etc.

b) Provide structural details for new egress opening in existing wall.

c) Provide details for foundations , slab, ventilation, lighting, etc. at new egress door & for new riser room.

d) Provide details for modification of existing egress route. Justify shaft enclosure rating per IBC 707.4.
08/29/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
08/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLEASE PROVIDE APPROVED REFERENCE PLAN SET FOR SHELL. THIS INFORMATION IS NECESSARY TO ADDRESS REMARKS ON PANEL SCHEDULE THAT PANELS AND TRANSFORMER WERE PROVIDED UNDER A SHELL PROJECT.
08/29/2011 LHANLY1 WATER REVIEW Passed
08/29/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/29/2011 LHANLY1 WWM REVIEW Passed
08/29/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Approved
08/29/2011 LEERAY HANLY ADA REVIEW Approved
12/02/2011 CPIERCE1 ENGINEERING REVIEW Needs Review
12/02/2011 CPIERCE1 ZONING REVIEW Needs Review
12/02/2011 CPIERCE1 FIRE REVIEW Needs Review