Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02785
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/26/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/26/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/26/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/26/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/26/2011 | RSHERRY1 | WWM | REVIEW | Passed | No new plumbing fixtures. |
| 08/26/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/29/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/29/2011 | RONALD BROWN | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/29/2011 | DAVE MANN | FIRE | REVIEW | Approved |