Permit Number: T11CM02719
Parcel: 110120960

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 3RD

Permit Number - T11CM02719
Review Name: REVISION - - 3RD
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02719
5301 E Grant Rd, Revision # 3

1. Electrical Sheet E 1201.2 indicates a change in rating of the AIC at ATS's 1 through 6 from 100K SCCR to 42K SCCR.
Must submit the AIC value at the ATS,s which allows the reduction. This was not included.

Ray T Majuta
DPSD, C of Tuc
Electrical Plan Review
12/07/2012
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2013 CPIERCE1 REJECT SHELF Completed