Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T11CM02719
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02719 5301 E Grant Rd, Revision # 3 1. Electrical Sheet E 1201.2 indicates a change in rating of the AIC at ATS's 1 through 6 from 100K SCCR to 42K SCCR. Must submit the AIC value at the ATS,s which allows the reduction. This was not included. Ray T Majuta DPSD, C of Tuc Electrical Plan Review 12/07/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/31/2013 | CPIERCE1 | REJECT SHELF | Completed |