08/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02719
5301 E Grant
Tucson Medical Center

1. Proposal #9,
A. "Revise SCCR for the Auto Transfer Switchs from 65,000 AIC to 45,000 AIC
B. Revise each ATS from open transition to closed
C. Provide 8 # 10,3/4 C from each ATS to RTU within the Electrical Room

for all above provide the electrical sheet these changes are to be made in and indicate by each delta why the change is made.
2. Proposal # 12, concerning the removal of the Lighting Protection System for the following Sheets E-521.1 through E-560.1, indicate on sheets submitted by the delta that "Lighting System removed".

Ray T Majuta
Elect Pln Ck
DSD, C of Tuc
8/14/2012
Ray.Majuta@tucsonaz.gov
08/21/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/24/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/24/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved