Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T11CM02719
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/14/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11CM02719 5301 E Grant Tucson Medical Center 1. Proposal #9, A. "Revise SCCR for the Auto Transfer Switchs from 65,000 AIC to 45,000 AIC B. Revise each ATS from open transition to closed C. Provide 8 # 10,3/4 C from each ATS to RTU within the Electrical Room for all above provide the electrical sheet these changes are to be made in and indicate by each delta why the change is made. 2. Proposal # 12, concerning the removal of the Lighting Protection System for the following Sheets E-521.1 through E-560.1, indicate on sheets submitted by the delta that "Lighting System removed". Ray T Majuta Elect Pln Ck DSD, C of Tuc 8/14/2012 Ray.Majuta@tucsonaz.gov |
| 08/21/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/24/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/24/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/06/2012 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |