Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T11CM02719
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEETS S203 AND A112.1
1. Please provide structural calculations for all the new retaining walls.
2. Provide sections through the stairs showing all accessible dimensions, railings, riser and tread dimensions and elevation differences.
a. Provide handrail elevation details.
SHEET A112.1
3. The serpentine concrete walk connection all the entrances is referenced to the development plan. The development plan has a different walk design.
4. The shade structure outside the stair well also is different than the development plan because it is not shown.
5. With the new revision elements and the items changed that are not shown, maybe a development plan revision is needed. Please contact John Beall.
END OF REVIEW
02/17/2012 ELIZABETH LEIBOLD ENGINEERING REVIEW Approved
02/21/2012 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/22/2012 GERARDO BONILLA REJECT SHELF Completed