Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM02719
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEETS S203 AND A112.1 1. Please provide structural calculations for all the new retaining walls. 2. Provide sections through the stairs showing all accessible dimensions, railings, riser and tread dimensions and elevation differences. a. Provide handrail elevation details. SHEET A112.1 3. The serpentine concrete walk connection all the entrances is referenced to the development plan. The development plan has a different walk design. 4. The shade structure outside the stair well also is different than the development plan because it is not shown. 5. With the new revision elements and the items changed that are not shown, maybe a development plan revision is needed. Please contact John Beall. END OF REVIEW |
| 02/17/2012 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Approved | |
| 02/21/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2012 | GERARDO BONILLA | REJECT SHELF | Completed |