Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02719
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2011 | ROBERT SHERRY | WATER | REVIEW | Passed | Private well system |
| 12/06/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/07/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Based on a rainfall rate of 3" per hour, the maximum roof area that can be accommodated by a 4" roof drain is 4613 square feet (Table 11-1, UPC 2006). Four 4"-roof drains and overflow drains, shown on sheet P232.1, are handling areas greater than 4613 square feet. Revise the sizes of those roof drains and overflow drains. [Second comment: Comment not resolved. Revise the roof drain sizing based on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour. Reference: Section 1101.11.1 and Table 11-1, UPC 2006.] [Original comment: Provide calculations to show how the roof drains and horizontal rainwater pipes were sized. Include the effect of side walls draining onto the roof. Reference: Sections 1101.11 and 1106.4, UPC 2006.] |
| 12/08/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire Pump detail on sheet FP202 shows test header in pump room. NFPA 20, section A.4.20.3.1 indicates hose valves should be outside pump room. Much more detail on piping arrangement will be required on sprinkler submitted. |
| 12/12/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/12/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/13/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/15/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/15/2011 | SUE REEVES | REJECT SHELF | Completed |