Permit Number: T11CM02719
Parcel: 110120960

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02719
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2011 ROBERT SHERRY WATER REVIEW Passed Private well system
12/06/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/07/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Based on a rainfall rate of 3" per hour, the maximum roof area that can be accommodated by a 4" roof drain is 4613 square feet (Table 11-1, UPC 2006). Four 4"-roof drains and overflow drains, shown on sheet P232.1, are handling areas greater than 4613 square feet. Revise the sizes of those roof drains and overflow drains. [Second comment: Comment not resolved. Revise the roof drain sizing based on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour. Reference: Section 1101.11.1 and Table 11-1, UPC 2006.] [Original comment: Provide calculations to show how the roof drains and horizontal rainwater pipes were sized. Include the effect of side walls draining onto the roof. Reference: Sections 1101.11 and 1106.4, UPC 2006.]
12/08/2011 MARTIN BROWN FIRE REVIEW Denied Fire Pump detail on sheet FP202 shows test header in pump room. NFPA 20, section A.4.20.3.1 indicates hose valves should be outside pump room. Much more detail on piping arrangement will be required on sprinkler submitted.
12/12/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/12/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/13/2011 STEVE SHIELDS ZONING REVIEW Approved