Permit Number: T11CM02705
Parcel: 133152870

Review Status: Active

Review Details: REVISION - - 1ST

Permit Number - T11CM02705
Review Name: REVISION - - 1ST
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied 1:RESOLVE PANEL RELOCATION SHEET E2.0: NOT IDENTIFIED.
2:PANEL B SHOWS A 60 AMP BREAKER IN SERVICE SWITCH GEAR, PANEL B SHOWS A LEAD OF 78 AMPS, HOWEVER THE SINGLE LINE SHOW A 200 AMP.

RAY MAJUTA
837-4988
10/12/2011 SREEVES1 FIRE REVIEW Needs Review