Permit Number: T11CM02705
Parcel: 133152870

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T11CM02705
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2011 JASON GREEN ENGINEERING REVIEW Approved
09/30/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Comment not resolved. Revise the site drawing to include the location, invert, and rim elevation of the manhole upstream of the connection to the public sewer (only the downstream manhole has been shown). Reference: City of Tucson Development Standard No. 2-01.0.0, Section 3.8 D and Section 103.2.3, UPC 2006.
10/05/2011 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Chase Bank @ Tanque Verde & Sabino Canyon - Expansion
T11CM02705
Site Plan (2nd Review)

TRANSMITTAL DATE: October 5, 2011

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for the areas of expansion and any changes to the site. Once a building square footage expansion calculation is provided that is cumulative to the last approved full code compliance site plan this comment may change.

2. D.S. 2-02.2.1.A.8 For the "NEW PAINTED PARKING STRIPS TO MATCH EXISTING" shown along the south side of the drive-thru provide the parking angle. Based on the provided last approved site plan showing 45 degree the space depth does not meet the required 18.7 feet, see LUC Section 3.3.6.4.A.

3. D.S. 2-02.2.2.A.3 Remove the lot coverage from the plan as it is not applicable for this project.

4. This comment was not addressed correctly. The building expansion calculation is not correct. Based on a 775 Sq. Ft. expansion to an existing 3,635 Sq. Ft building the percent of expansion would be 21.3 %, revise the calculation. D.S. 2-02.2.2.A.6 Provide a percentage of building area expansion calculation on the site plan. If the building has been previously expanded, those calculations shall be included.

5. As this site plan has not been approved remove all revision clouds and deltas from the plan.

6. Once the above comments have been correctly addressed zoning will provide an over-the-counter review. Call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\2011\t11cm02705
10/05/2011 ANDREW CONNOR LANDSCAPE REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
10/11/2011 SUE REEVES REJECT SHELF Completed