Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02699
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2011 | RONALD BROWN | ADA | REVIEW | Denied | SHEETS A 4.1 and A5.1 1. As a general reference for accessible standards, dimensions and clearances, note 2 is too general and not acceptable. Please provide either: a. Code compliant requirements of the 2010 ADA Standards for Accessible Design (Dimensions, clearances and accessories) to each of the design elevations and floor plans or b. Provide detail references from each design detail to the specific relative detail shown on sheet G0.06 showing accurate and specific accessible requirements for the detail. 2. If option "b" is initiated, please provide a thorough compliance review of all the G0.06 details and a note on sheet G0.6 to the effect that all the reference details shown are exact duplications of the 2010 ADA Standards for Accessible Design and the contractor may rely on their accuracy for construction. Examples for clarification: a. The water cooler detail shown in reference detail 19/EWC-DF is not the same as detail 13/A5.1 b. Details 1, 4, 8, 5, 12, and 14 do not meet the clearance requirement of detail 8/G0.06. Please provide a large scale section detail of the vanity with sink showing compliance with 2010 ADASAD, Sections 606.2, 606.3, 305 and 306. END OF REVIEW |
| 11/21/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | Reference ADA folder for comments |
| 11/22/2011 | GERRY KOZIOL | WWM | REVIEW | Denied | NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER. NEED RD FLOOR PCRWRD REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER- CHAD AMATEAU- 740-6547 MAY NEED PUBLIC SEWER CONSTRUCTION PERMIT FOR PUBLIC SEWER ALTERATIONS- YVONNE SUAREZ - 740-6733 NEED PCRWRD 3RD FLOOR CAPACITY REVIEW - KURT STEMM - 740-6534 NEED WASTEWATER IWC REVIEW & APPROVAL - TOM TOMCHAK - 5025 W INA RD - 4436200 |
| 11/22/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/22/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The size of the vent must be increased by one pipe size over its entire length to avoid the length limitations imposed by Table 7-5, UPC 2006 (see footnote for Table 7-5). [Second comment: Comment not resolved; the 2" vent for the acid neutralization tank has a horizontal length greater than 40-feet.] [Original comment: Verify that the horizontal portions of the plumbing vents do not exceed 1/3 of the total allowable vent length shown in Table 7-5, UPC 2006.] |
| 11/28/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 12/08/2011 | SUE REEVES | REJECT SHELF | Completed |