Permit Number: T11CM02699
Parcel: 11706081A

Address:
290 E 8TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02699
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Reference ADA folder for comments
11/21/2011 RONALD BROWN ADA REVIEW Denied SHEETS A 4.1 and A5.1
1. As a general reference for accessible standards, dimensions and clearances, note 2 is too general and not acceptable. Please provide either:
a. Code compliant requirements of the 2010 ADA Standards for Accessible Design (Dimensions, clearances and accessories) to each of the design elevations and floor plans
or

b. Provide detail references from each design detail to the specific relative detail shown on sheet G0.06 showing accurate and specific accessible requirements for the detail.
2. If option "b" is initiated, please provide a thorough compliance review of all the G0.06 details and a note on sheet G0.6 to the effect that all the reference details shown are exact duplications of the 2010 ADA Standards for Accessible Design and the contractor may rely on their accuracy for construction. Examples for clarification:
a. The water cooler detail shown in reference detail 19/EWC-DF is not the same as detail 13/A5.1
b. Details 1, 4, 8, 5, 12, and 14 do not meet the clearance requirement of detail 8/G0.06. Please provide a large scale section detail of the vanity with sink showing compliance with 2010 ADASAD, Sections 606.2, 606.3, 305 and 306.
END OF REVIEW
11/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The size of the vent must be increased by one pipe size over its entire length to avoid the length limitations imposed by Table 7-5, UPC 2006 (see footnote for Table 7-5).
[Second comment: Comment not resolved; the 2" vent for the acid neutralization tank has a horizontal length greater than 40-feet.]
[Original comment: Verify that the horizontal portions of the plumbing vents do not exceed 1/3 of the total allowable vent length shown in Table 7-5, UPC 2006.]
11/22/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/22/2011 GERRY KOZIOL WWM REVIEW Denied NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER. NEED RD FLOOR PCRWRD REVIEW OF LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER- CHAD AMATEAU- 740-6547 MAY NEED PUBLIC SEWER CONSTRUCTION PERMIT FOR PUBLIC SEWER ALTERATIONS- YVONNE SUAREZ - 740-6733
NEED PCRWRD 3RD FLOOR CAPACITY REVIEW - KURT STEMM - 740-6534
NEED WASTEWATER IWC REVIEW & APPROVAL - TOM TOMCHAK - 5025 W INA RD - 4436200
11/28/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/08/2011 SUE REEVES OUT TO CUSTOMER Completed
12/08/2011 SUE REEVES REJECT SHELF Completed