Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Detail 8A:
a. Need sloped handrail both sides of ramp
b. Show hand rail elevation, show 4" high horizontal bar as per ANSI, Section 405.9 (b)
2. Detail 7A:
a. Need handrails both side of ramp
b. Ditto 2b
c. Show handrails in section
3. Provide Street Identification
4. Show slopes of marked crossing as per Section 403.3
5. Detail 3 and 4, show bottom of main accessible sign at 7'-0" a.f.g.
6. Detail 6, show maximum slope of accessible parking and aile area at 2% maximum as per Section 502.5.
END OF REIVEW
11/07/2011 RONALD BROWN ADA REVIEW Passed
11/08/2011 CPIERCE1 ZONING REVIEW Needs Review
11/08/2011 CPIERCE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2011 CPIERCE1 OUT TO CUSTOMER Completed