Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02683
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2011 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/25/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. |
| 08/25/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 08/25/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/25/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/25/2011 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/25/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006 |
| 08/25/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 08/25/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/13/2011 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 09/13/2011 | GBONILL1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |