Permit Number: T11CM02683
Parcel: 11615082A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02683
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2011 DAVID RIVERA ZONING REVIEW Approved
08/25/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust fans to show that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
08/25/2011 ERIC NEWCOMB ADA REVIEW Passed
08/25/2011 ROBERT SHERRY WATER REVIEW Approved
08/25/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/25/2011 LOREN MAKUS ENGINEERING REVIEW Approved
08/25/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006
08/25/2011 DAVE MANN FIRE REVIEW Approved
08/25/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/13/2011 GBONILL1 WWM REVIEW Needs Review
09/13/2011 GBONILL1 ELECTRICAL-COMMERCIAL REVIEW Needs Review