Permit Number: T11CM02662
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11CM02662
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2011 DAVE MANN FIRE REVIEW Approved
08/26/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
08/26/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/26/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP A3.1 Why does front elevation show panels in landscape while layout is in portrait.

Provide actual cutsheets for Schletter Fix-V brackets. Calculations, A pages, S pages and roof sections do not all conform on size. The problem here may be that Schnieder documents from Schletter are for a different bracket.

Provide details for which "V" page applys to structural arrays C1 - C5.2 (A pages call them N-D)

Provide layout of Fix-V brackets on S pages to correspond to required # of brackets on "V" pages.

Provide layout or information for array N1-N3 racking where you intend to use more or less than the 16 panels array on pp V.02 (similar to pp s1.11 for building 1 would be excellent)

Clarify front elevation with panels in landscape on pp v.02
08/26/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/21/2011 SUE REEVES REJECT SHELF Completed