Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM02661
Parcel: 13314227C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02661
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2011 SREEVES1 ADA REVIEW Passed
08/25/2011 GERRY KOZIOL WWM REVIEW Approved
08/25/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/26/2011 DAVE MANN FIRE REVIEW Approved
08/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) Provide 1 line diagrams.

2) Provide complete panel schedules for all panels being modified and for all upstream panels where there are additonal loads. Panel schedules to include amperage rating, supply voltage, source loads, installed loads, and complete load calculations.

3) Balance phases within a load center to within 15% per C.O.T. ordinance

4) Coordinate ckt call outs on all sheets. (is it panel 'OR or OR1)
08/30/2011 LHANLY1 WATER REVIEW Denied Provide water use calculations for added fixtures. Verify existing domestic water may handle additonal new fixtures at restroom.
08/30/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied 1) Clarify in general notes what references are to plans not provided (P2.2 & P2.4).

2) Coordinate with cover sheet information which plumbing code you intend to use

3) Clarify use of 1/2" insulation on hot water line (IECC 504.5)

4) Provide complete isometric drawings for restrooms domestic water and drain-waste system

5) Plumbing fixture schedule is incomplete. Provide all necessary information for lavatories, water closets and urinals.
08/30/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP A-2

a) Keynote 2....door must have panic hardware as it is not a main exit complying with 1008.1.8.3

b) Clarify use of keynote 4, are you considering this an assembly area? If so then please justify occupant load of 25 and single exit out of space.

c) Provide details for listed 3 hour exit passageway infill.

d) Keynote 8 in womens 108 appears to be indicating work outside of this area.

PP A-4

a) Elevations need to provide actual location or min/max dimensions. Example--vertical grab bar is shown as 39" min from rear wall; implication is that there is no maximum.
08/30/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied 1) PP M001

a) Clarify keynote 1 placed in conference room. Where is 6" round duct indicated?

b) Clarify keynote 3 in conference room & keynote 12 @ c-19

c) Please review all keynotes, key locations and information. It appears your overlay has not been proofed.

2) Clarify how to work this drawing M2.2 (not provided)

3) Proof your diffuser, register & grille schedule on pp M-003 as it does not coordinate with floor plan.

4) Indicate volume of outside air and how it is to be balanced at each AC supply.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/09/2011 SUE REEVES REJECT SHELF Completed