Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02661
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/25/2011 | SREEVES1 | ADA | REVIEW | Passed | |
08/25/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/25/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/26/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
08/29/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) Provide 1 line diagrams. 2) Provide complete panel schedules for all panels being modified and for all upstream panels where there are additonal loads. Panel schedules to include amperage rating, supply voltage, source loads, installed loads, and complete load calculations. 3) Balance phases within a load center to within 15% per C.O.T. ordinance 4) Coordinate ckt call outs on all sheets. (is it panel 'OR or OR1) |
08/30/2011 | LHANLY1 | WATER | REVIEW | Denied | Provide water use calculations for added fixtures. Verify existing domestic water may handle additonal new fixtures at restroom. |
08/30/2011 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1) Clarify in general notes what references are to plans not provided (P2.2 & P2.4). 2) Coordinate with cover sheet information which plumbing code you intend to use 3) Clarify use of 1/2" insulation on hot water line (IECC 504.5) 4) Provide complete isometric drawings for restrooms domestic water and drain-waste system 5) Plumbing fixture schedule is incomplete. Provide all necessary information for lavatories, water closets and urinals. |
08/30/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PP A-2 a) Keynote 2....door must have panic hardware as it is not a main exit complying with 1008.1.8.3 b) Clarify use of keynote 4, are you considering this an assembly area? If so then please justify occupant load of 25 and single exit out of space. c) Provide details for listed 3 hour exit passageway infill. d) Keynote 8 in womens 108 appears to be indicating work outside of this area. PP A-4 a) Elevations need to provide actual location or min/max dimensions. Example--vertical grab bar is shown as 39" min from rear wall; implication is that there is no maximum. |
08/30/2011 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1) PP M001 a) Clarify keynote 1 placed in conference room. Where is 6" round duct indicated? b) Clarify keynote 3 in conference room & keynote 12 @ c-19 c) Please review all keynotes, key locations and information. It appears your overlay has not been proofed. 2) Clarify how to work this drawing M2.2 (not provided) 3) Proof your diffuser, register & grille schedule on pp M-003 as it does not coordinate with floor plan. 4) Indicate volume of outside air and how it is to be balanced at each AC supply. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/09/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
09/09/2011 | SUE REEVES | REJECT SHELF | Completed |