Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T11CM02660
Parcel: 13314227C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02660
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2011 SREEVES1 ADA REVIEW Passed
08/25/2011 GERRY KOZIOL WWM REVIEW Denied NEED TO CLARIFY DRAWINGS SHOWING EXSISTING WASTEWATER PLUMBING FIXTURES REMOVED FOR CREDIT
NEED 5TH FLOOR CREDIT EVALUATION
08/25/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/26/2011 DAVE MANN FIRE REVIEW Approved
08/29/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Provide 1-line diagrams and completed panel schedules for all new work. Any panel with additional loads must also have complete panel schedule and load calcs for any upstream feeder panels.

Each panel shall be phase balanced within 15% per C.O.T. ordinance

Clarify removed loads v. added loads & total loads at each panel.
08/30/2011 LHANLY1 WATER REVIEW Approved
08/30/2011 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Denied General notes indicate you are using the 2006 IPC and the 1997 UPC while cover sheet calls for 2006 UPC. Pick either the 2006 UPC or the 2006 IPC for all new work.

Clarify if hot water system is recirculating or not. 1/2" of insulation on hot water piping may be insuficient (GN 6.3)

Clarify lack of information for fixtures P4 & P5 and added information for unused P3.

Provide details for new shower installation to include domestic water piping, waste piping, controls, etc.
08/30/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP A-2

a) keynote 2....provide panic hardware. Signage per IBC 1008.1.8.3 is for main exits only.

b) what is keynote 5 by office 111? Should it be keynote 6?

c) keynote 9...Please provide details for listed 3 hour assembly at exit passageway infill

d) keynote 11 "provide ADA compliant...", do you mean accessible? Please provide cut sheets or details for prefabricated shower insert...to include threshold detail.

PPA-4

a) If you are going to list minimum or maximum dimensions then you must also show associated maximum or minimum dimensions as applicable. If you use a dimension within the allowed range then please delete extraneous, misleading notations. eg..water closet is not 18" minimum from side wall as noted, but should be 18" or 16" min-18" max.
08/30/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Denied PP M-002

a) Explain reference to drawing M2.1 in keynote 1. No such drawings supplied for reference.

b) Keynote 4 data does not match info shown on floor plan

c) Data on floor plans soes not coordinate with data in keynotes.

d) Where do keynotes actually apply as many oare outside of const area, and some appear to be required at 2 locations.

e) Please clarify keynote 12 as plans do not indicate any new duct work at specified location.

f) Please clarify how outside air requirements are going to be met. Where is OA inlet and what should it be set at?

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/09/2011 SUE REEVES REJECT SHELF Completed