Permit Number: T11CM02657
Parcel: 13001004B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02657
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2011 RONALD BROWN ADA REVIEW Passed
09/15/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations and details for the water heater brackets, platform and connection to existing joists.
2. Please provide dimensions on the for plan for all new partitions including the toilets.
3. Please provide ceramic tile on the side elevation of the toilet showing compliance with the 2006 IBC, Section 1210.2.
END OF REVIEW
09/15/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/22/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for business occupancy (a bottled water dispenser is not recognized as a substitute for a drinking fountain). Reference: Sections 1109.5 and 2902.1, IBC 2006.
2. Clarify where details 1/M6.2 and 2/M6.2 occur (WH-1a and WH-1b on sheet M9.2?). Reference: Section 106.3.1, IPC 2006.
3. Revise the plumbing floor plan on sheet M3.2 to show all of the natural gas pipe sizes. Reference: Sections106.3.1 and 402.1, IFGC 2006.
4. Provide a vacuum relief valve for bottom-fed storage-type water heaters. Reference: Section 504.2, IPC 2006.
5. An emergency eyewash/shower is a plumbing fixture. Provide a connection of the emergency eyewash/shower to the sanitary drainage system. Reference: Section 301.3, IPC 2006.
6. Correct detail 5/M6.2; an emergency eyewash/shower shall not be supplied with water from the fire sprinkler system. Reference: Sections 602.2 and 608.9, IPC 2006.
7. Special inspections for medical gas installation shall be performed by companies recognized by the City of Tucson as being qualified to perform such inspections.
09/22/2011 ROBERT SHERRY WATER REVIEW Denied Show the location of the water meter and the reduced pressure backflow assembly on the drawings and indicate their sizes. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
09/23/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
2. Coordinate the mechanical air flow diagram (1/M8.1) with the equipment shown on the mechanical HVAC floor Plan on sheet M1.1.
3. Provide the information regarding the nature of the materials and fumes being exhausted from the lab. Reference: Sections 106.3.1 and 502.1, IMC 2006.
09/27/2011 GERRY KOZIOL WWM REVIEW Approved
09/30/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11CM02657
1956 E Silverlake Rd,
TI Lab and Warehouse,

Provide a discription of the process of operation and materials used. Most intrested in compliance with Article 500 of 2005 NEC.
The second service being supplied from Building 1974 to Building1956 does not comply with 2005 NEC 230.2(D) as noted on Sheet E4.0. The service supplied is the same voltage, 120/208 3 phase as feeding the buiilding currently. The difference is that the sevice once on the building is transformed into a different voltage (277/480v). The service entrance conductors to the building are required to be of a different voltage.

Ray T Majuta,
Elect Plan Review,
PDSD, City of Tucson
10/3/2011
Ray@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
10/04/2011 DELMA ROBEY OUT TO CUSTOMER Completed
10/04/2011 SUE REEVES REJECT SHELF Completed