Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02654
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02654
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/07/2011 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved hydrogen expulsion rate from battery pack shown to be .0003 cf per hour in 720 cf space. No exhaust vent needed.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2011 SUE REEVES APPROVAL SHELF Completed
10/20/2011 GERARDO BONILLA OUT TO CUSTOMER Completed