Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02654
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2011 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | hydrogen expulsion rate from battery pack shown to be .0003 cf per hour in 720 cf space. No exhaust vent needed. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/20/2011 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/20/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |