Permit Number: T11CM02654
Parcel: 13216600A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02654
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1 Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. [Original Comment: Show the size, routing, and termination of the condensate drains for the air handling units. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.]
2 Comment not resolved. Show how the hydrogen concentration in the room will be limited to less than 1.0 % of the total room volume. Reference: Section 502.4.1, IMC 2006. [Original comment: Provide specifications for the proposed storage batteries and show how the ventilation in the communications room complies with the requirements of Section 502.4, IMC 2006.]
10/06/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2011 GERARDO BONILLA OUT TO CUSTOMER Completed