Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2011 MARTIN BROWN FIRE REVIEW Approved
08/31/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide product specifications for the proposed air handling units; the provided specifications are for a gas-fired furnace. Reference: Section 106.3.1, IMC 2006.
2. Show the size, routing, and termination of the condensate drains for the air handling units. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006.
3. Provide specifications for the proposed storage batteries and show how the ventilation in the communications room complies with the requirements of Section 502.4, IMC 2006.
09/09/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/14/2011 STEVE SHIELDS ZONING REVIEW Approved
09/20/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved REVIEWED BY DAN SANTA-CRUZ