Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11CM02654
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/31/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide product specifications for the proposed air handling units; the provided specifications are for a gas-fired furnace. Reference: Section 106.3.1, IMC 2006. 2. Show the size, routing, and termination of the condensate drains for the air handling units. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. 3. Provide specifications for the proposed storage batteries and show how the ventilation in the communications room complies with the requirements of Section 502.4, IMC 2006. |
| 09/09/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/14/2011 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/20/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | REVIEWED BY DAN SANTA-CRUZ |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/29/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/29/2011 | SUE REEVES | REJECT SHELF | Completed |