Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T11CM02627
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2011 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN REVIEW COMMENTS Date: 9-19-11 Activity: T11CM02627 Address: 10701 E Nebraska Applicant: Den Bedient Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken. SCOPE OF REVIEW: The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval. GENERAL REQUIREMENTS: 1. Specify safety glazing in pool area per R308.4(5) as amended. 2. Include weight of roof mounted solar collectors/tanks in roof truss design, R801.2. 3. Provide at least one GFCI protected receptacle between 5 and 10 feet from water's edge, E4103.1.5. If you have any questions please contact: Clayton Trevillyan 520.837.4913 Residential Plan Review |