Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02617
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/15/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/15/2011 | GERRY KOZIOL | WWM | REVIEW | Approved |