Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11CM02616
Parcel: 110050380

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02616
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2011 GERRY KOZIOL WWM REVIEW Approved
08/22/2011 DAVE MANN FIRE REVIEW Approved
08/31/2011 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide drinking fountains as per 2006 IBC, Section 1109.5, Table 2902.1 and ICC/ANSI 117.1, Section 602.
2. Provide structural calculations and bracket details for the wall mounted water heater.
3. Provide special inspection certifications.
END OF REVIEW
08/31/2011 ROBERT SHERRY WATER REVIEW Approved
08/31/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the location and water service to the wall box P4. The drawing on sheet P1.0 appears to show a drain line for it but no water supply; neither water supply nor drain is shown on the riser diagrams on sheet P3.0. Reference: Section 106.3.1, IPC 2006.
2. Show the location of the point of use water dispenser noted in the Code Review on sheet A1.0. Reference: Section 106.3.1, IPC 2006.
3. Appliances (e.g. coffee machines, commercial ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2006.
08/31/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/20/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved BY DAN SANTA-CRUZ