Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T11CM02616
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/22/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
08/31/2011 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Provide drinking fountains as per 2006 IBC, Section 1109.5, Table 2902.1 and ICC/ANSI 117.1, Section 602. 2. Provide structural calculations and bracket details for the wall mounted water heater. 3. Provide special inspection certifications. END OF REVIEW |
08/31/2011 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/31/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the location and water service to the wall box P4. The drawing on sheet P1.0 appears to show a drain line for it but no water supply; neither water supply nor drain is shown on the riser diagrams on sheet P3.0. Reference: Section 106.3.1, IPC 2006. 2. Show the location of the point of use water dispenser noted in the Code Review on sheet A1.0. Reference: Section 106.3.1, IPC 2006. 3. Appliances (e.g. coffee machines, commercial ice makers, etc) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2006. |
08/31/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
09/20/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | BY DAN SANTA-CRUZ |