Permit Number: T11CM02615
Parcel: 12620001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02615
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied Response to original comment incomplete.

"SHOW VERIFICATION OF REQUIRED POINT LOAD CAPACITY NOTED ON 'V' PAGES BY SCHLETTER.

Response is that 218# down is allowed and 194.5# down was addressed in original calculations, problem is that max downward point load on V pages is 579 #'s as noted on pp V.09. This is greater than than calculated 218#'s allowed.

Similarly the up load addressed in the structural addendum is calculated from a design load of 285.6# while the Schletter documents indicate that the maximum uplift could be as high as 883.3# on pp V.09.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
12/02/2011 SUE REEVES REJECT SHELF Completed