Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02615
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/22/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | Response to original comment incomplete. "SHOW VERIFICATION OF REQUIRED POINT LOAD CAPACITY NOTED ON 'V' PAGES BY SCHLETTER. Response is that 218# down is allowed and 194.5# down was addressed in original calculations, problem is that max downward point load on V pages is 579 #'s as noted on pp V.09. This is greater than than calculated 218#'s allowed. Similarly the up load addressed in the structural addendum is calculated from a design load of 285.6# while the Schletter documents indicate that the maximum uplift could be as high as 883.3# on pp V.09. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/02/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 12/02/2011 | SUE REEVES | REJECT SHELF | Completed |