Permit Number: T11CM02608
Parcel: 13809007G

Review Status: Completed

Review Details: OTHER

Permit Number - T11CM02608
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide indirect waste receptors for the sanitizing compartments of the 3-compartment sinks. Reference: section 801.2, UPC 2006.
2. Verify the size of the gravity grease interceptor complies with the requirements of Table 10-3, UPC 2006 but is not over-sized.
10/11/2011 CPIERCE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/11/2011 CPIERCE1 OUT TO CUSTOMER Completed