Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T11CM02608
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/19/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide indirect waste receptors for the sanitizing compartments of the 3-compartment sinks. Reference: section 801.2, UPC 2006. 2. Verify the size of the gravity grease interceptor complies with the requirements of Table 10-3, UPC 2006 but is not over-sized. |
10/11/2011 | CPIERCE1 | WWM | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/11/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |