Permit Number: T11CM02578
Parcel: 128102960

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T11CM02578
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2011 DAVID RIVERA ZONING REVIEW Approved
08/17/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the ventilation calculations to reflect the actual use of room 124:telephone/data entry, not office space. Reference: Table 6-1, ASHRAE Standard 62.1-2004.
08/17/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/17/2011 ROBERT SHERRY WATER REVIEW Approved
08/17/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D3.1; CODE REVIEW (PLUMBING FIXTURES): INCLUDE DRINKING FOUNTAINS IN THE PLUMBING FIXTURES (REQUIRED AND PROVIDED).
2. SHEET D3.1; CODE REVIEW (TENANT LOAD): CHECK THE OCCUPANCY LOAD STATED ON SHEET D3.1 COMPARED TO THE LAYOUT SHOWN ON SHEET A3.1 FLOOR PLAN.
3. SHEET D3.1; CODE REVIEW (TENANT LOAD): THE TENANT LOAD IS LISTED AS 123 OCCUPANTS, AND SHOULD BE 248. REVISE.
4. SHEET D3.1: PER THE 2006 IBC, SECTION 3409.7, INDICATE ON THE DRAWINGS HOW A MAXIMUM OF 20% OF THE VALUATION ON THIS PROJECT IS SPENT ON ACCESSIBILITY.
5. GENERAL: SHOW EGRESS AND NUMBER OF OCCUPANTS EXITING AT EACH LOCATION. INCLUDE OCCUPANTS FROM THE SECOND FLOOR.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/17/2011 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
08/17/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/17/2011 JASON GREEN ENGINEERING REVIEW Approved
08/17/2011 DAVE MANN FIRE REVIEW Denied Occupant load must be based on number of actual seats. Please provide exiting diagram with loads and dimensions.
08/17/2011 ERIC NEWCOMB ADA REVIEW Passed
08/17/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed