Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11cm02571

1. Where is Panel PP fed from? Different service?
2. Panel PPWIN shows 200 amp rating with a 225 amp feed from generator ?
3. Panel PP shows 100 amp rating with a 100 amp feed from generator ?
4. Does the generator fall under 2005 NEC 702.8 and are signs regarding A and B required ?
5. Describe grounding concerning the ATS and panels fed.
Ray T Majuta
Elect Plan Ck
PDSD, C of Tucson
10/22/2012