Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T11CM02571
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/22/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T11cm02571 1. Where is Panel PP fed from? Different service? 2. Panel PPWIN shows 200 amp rating with a 225 amp feed from generator ? 3. Panel PP shows 100 amp rating with a 100 amp feed from generator ? 4. Does the generator fall under 2005 NEC 702.8 and are signs regarding A and B required ? 5. Describe grounding concerning the ATS and panels fed. Ray T Majuta Elect Plan Ck PDSD, C of Tucson 10/22/2012 Ray.Majuta@tucsonaz.gov |
11/07/2012 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/07/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |