Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T11CM02571
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/06/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved. Show how the hydrogen concentration in the room will be limited to less than 1.0 % of the total room volume. Reference: Section 502.4.1, IMC 2006. [Original comment: IMC 502 -- Provide verification of correct ventilation for battery storage area] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/07/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |