Permit Number: T11CM02571
Parcel: 14101005E

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T11CM02571
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2011 PETER MCLAUGHLIN PLANNING-CITY HALL REVIEW Passed
09/20/2011 JASON GREEN ENGINEERING REVIEW Approved
09/20/2011 MICHAEL ST. PAUL ZONING REVIEW Passed
09/21/2011 MARTIN BROWN FIRE REVIEW Approved Plans include note regarding future installation of propane tank. When this happens, a separate tank permit issued through the fire department will be required.
09/22/2011 LHANLY1 COMMUNICATIONS REVIEW Passed NO CHANGES TO COMMUNICATION EQUIPMENT ON THIS ACTIVITY
09/22/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied NEC 700 -- PROVIDE INFORMATION FOR ALL ELECTRICAL SYSTEMS INCLUDING PROPOSED INTEGRATED DC POWER SYSTEM NOTED ON PP C-2. INCLUDE ALL CHARGER, AND TRANSFER INFORMATION.

IMC 502 -- PROVIDE VERIFICATION OF CORRECT VENTILATION FOR BATTERY STORAGE AREA

ERRATA -- KEYNOTES PP E2.1 ON FLOOR PLAN CALLED OUT AS 6 & 7 SHOULD REFERENCE 2 & 3
09/22/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2011 CPIERCE1 APPROVAL SHELF Completed
09/29/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/29/2011 CPIERCE1 REJECT SHELF Completed