Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T11CM02571
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2011 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Passed | |
| 09/20/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/20/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 09/21/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | Plans include note regarding future installation of propane tank. When this happens, a separate tank permit issued through the fire department will be required. |
| 09/22/2011 | LHANLY1 | COMMUNICATIONS | REVIEW | Passed | NO CHANGES TO COMMUNICATION EQUIPMENT ON THIS ACTIVITY |
| 09/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | NEC 700 -- PROVIDE INFORMATION FOR ALL ELECTRICAL SYSTEMS INCLUDING PROPOSED INTEGRATED DC POWER SYSTEM NOTED ON PP C-2. INCLUDE ALL CHARGER, AND TRANSFER INFORMATION. IMC 502 -- PROVIDE VERIFICATION OF CORRECT VENTILATION FOR BATTERY STORAGE AREA ERRATA -- KEYNOTES PP E2.1 ON FLOOR PLAN CALLED OUT AS 6 & 7 SHOULD REFERENCE 2 & 3 |
| 09/22/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/29/2011 | CPIERCE1 | APPROVAL SHELF | Completed |
| 09/29/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/29/2011 | CPIERCE1 | REJECT SHELF | Completed |