| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/07/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | INFORMATION PROVIDED SHOWING HYDROGEN LEVELS COULD NOT REACH 1% OF ROOM VOLUME (.0003 CF PER HOUR AVAILABLE FOR ROOM OVER 720 CF IN VOLUME) |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/20/2011 | SUE REEVES | APPROVAL SHELF | Completed |