Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T11CM02570
Parcel: 13401002D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11CM02570
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied Comment not resolved. Show how the hydrogen concentration in the room will be limited to less than 1.0 % of the total room volume. Reference: Section 502.4.1, IMC 2006. [Original comment: Provide verification that battery bank installation meets IMC section 502 criteria for venting]

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2011 GERARDO BONILLA OUT TO CUSTOMER Completed