Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T11CM02570
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2011 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Passed | |
| 09/20/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/20/2011 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
| 09/21/2011 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/22/2011 | LHANLY1 | COMMUNICATIONS | REVIEW | Passed | NO WORK BEING DONE TO COMMUNNICATIONS EQUIPMENT ON THIS ACTIVITY |
| 09/22/2011 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | ELECTRICAL PAGES NEED TO BE SEALED BY ENGINEER PROVED DATA SHEETS, CONNECTION INFORMATION, ETC. FOR INTEGRATED BATTERY POWER SYSTEM NOTED ON PP C2 PER NEC SECTION 700 PROVIDE VERIFICATION THAT BATTERY BANK INSTALLATION MEETS IMC SECTION 502 CRITERIA FOR VENTING ERRATA-- KEYNOTE REFERENCE 9 ON PP E3.1 AT DISCONNECT, DO YOU MEAN KEYNOTE 8? ERRATA-- PP C2 INDICATES 300 A PCWIN PANEL, WHILE ELECTRICAL PAGES INDICATE 225 A PANEL. |
| 09/22/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/29/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/29/2011 | SUE REEVES | REJECT SHELF | Completed |